Difference between revisions of "Midea"

From CoolAutomation Wiki
Jump to navigation Jump to search
Line 3: Line 3:
 
[[File:CMNet-midea-VRF-connection.png]]
 
[[File:CMNet-midea-VRF-connection.png]]
 
<br>
 
<br>
'''Outdoor Switch SW3-1 must be ON for proper operation of CoolMasterNet connected to XYE bus.'''
+
'''<span style="color:red">Outdoor Switch SW3-1 must be ON for proper operation of CoolMasterNet connected to XYE bus.</span>'''
 
<br><br>
 
<br><br>
 
----
 
----

Revision as of 02:29, 31 March 2016

Connecting to Midea VRF system

  • If CoolMasterNet is the only central controller in the system:

CMNet-midea-VRF-connection.png
Outdoor Switch SW3-1 must be ON for proper operation of CoolMasterNet connected to XYE bus.



  • If two central controllers should be connected:

CMNet-midea-VRF-connection2.png

We recommend to connect to line L7 on CoolMasterNet. Lines L4, L5, L6 can also be used.