Connecting to Midea VRF system

  • If CoolMasterNet is the only central controller in the system:

CMNet-midea-VRF-connection.png
Outdoor Switch SW3-1 must be ON for proper operation of CoolMasterNet connected to XYE bus.



  • If two central controllers should be connected:

CMNet-midea-VRF-connection2.png

We recommend to connect to line L7 on CoolMasterNet. Lines L4, L5, L6 can also be used.