Modbus RTU

From CoolAutomation Wiki
Jump to navigation Jump to search

The Modbus functionality of CoolMasterNet is fully described in Modbus Guidelines document

Modbus RTU Configuration

CoolMasterNet Modbus RTU is activated with below command:

>line type L3 CG5
OK, Boot Required!
>

CoolMasterNet has to be restarted to run Modbus RTU for the first time. To quire current Modbus RTU configuration use line command:

>line

L1: SA Master U00/G00 myid:E5
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L2: DK Slave U00/G00 myid:0B
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L3: CG5 Modbus Address:0x40(64) 9600_8N1
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L4: MH SLink:N U00/G00 myid:C900
Tx:0/2 Rx:0/2 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L5: Unused
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L6: Unused
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L7: LG Master U00/G00
Tx:983/1066 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L8: Unused
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
OK
>

The rest is similar between Modbus RTU and Modbus IP. Follow the link to VA Concept.