Difference between revisions of "Samsung"
| Line 448: | Line 448: | ||
|- | |- | ||
| style="text-align: center; " | 261 | | style="text-align: center; " | 261 | ||
| + | | Digital COMP_discharge Sensor breakaway Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 262 | ||
| + | | Fixd COMP1_discharge Sensor breakaway Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 263 | ||
| + | | Fixd COMP2_discharge Sensor breakaway Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 264 | ||
| + | | Fixd COMP3_discharge Sensor breakaway Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 265 | ||
| + | | SUMP temperature sensor breakaway (Main) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 266 | ||
| + | | SUMP temperature sensor breakaway (Sub1) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 267 | ||
| + | | High Pressure SENSOR breakaway ERROR | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 268 | ||
| + | | SUMP temperature sensor breakaway (Sub3) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 269 | ||
| + | | SUCTION Sensor breakaway | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 271 | ||
| + | | Digital COMP Sump_temperature Digital SENSOR ERROR (OPEN/SHORT) | ||
| + | - ERROR detect Condition: detect outdoor temperature -10oC | ||
| + | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 276 | ||
| + | | FIXED COMP1 Sump_temperature SENSOR ERROR (OPEN/SHORT) | ||
| + | - ERROR detect Condition: detect outdoor temperature more than -10oC | ||
| + | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 277 | ||
| + | | FIXED COMP2 Sump_temperature SENSOR ERROR (OPEN/SHORT) | ||
| + | - ERROR detect Condition: detect outdoor temperature -10oC | ||
| + | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 278 | ||
| + | | FIXED COMP3 Sump_temperature FIXED 3 SENSOR ERROR (OPEN/SHORT) | ||
| + | - ERROR detect Condition: detect outdoor temperature more than -10oC | ||
| + | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 291 | ||
| + | | High pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect | ||
| + | (shortError: less than 0.4v, Error detect), (OPENError: over 4.2v, Error detect) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 296 | ||
| + | | Low Pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect | ||
| + | (shortError: less than 0.4v, Error detect), (OPENError:over 4.7v, Error detect) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 301 | ||
| + | | High Pressure SENSOR breakaway ERROR | ||
| + | | | ||
| + | |- | ||
| + | |||
| + | | style="text-align: center; " | 306 | ||
| + | | Low Pressure SENSOR breakaway ERROR | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 307 | ||
| + | | Oil Balance Sensor SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 308 | ||
| + | | SUCTION Sensor SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 309 | ||
| + | | Oil Balace Sensor2 Sensor SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 310 | ||
| + | | Oil Balance Sensor3 Sensor SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 311 | ||
| + | | Double pipe Sensor SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 312 | ||
| + | | Main Cooling Sol Valve Open Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 313 | ||
| + | | 4-Way Valve operation Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 314 | ||
| + | | Oil Balace Sensor4 SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 315 | ||
| + | | CT1 Sensor Short or Open | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 316 | ||
| + | | CT2 Sensor Short or Open | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 317 | ||
| + | | CT3 Sensor Short or Open | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 320 | ||
| + | | OLP Sensor SHORT / OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 321 | ||
| + | | EVI INLET Sensor SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 322 | ||
| + | | EVI OUTLET Sensor SHORT/OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 323 | ||
| + | | Error on suction sensor 2 (Short or Open) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 324 | ||
| + | | Outdoor Unit Fan Motor Current Sensor SHORT / OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 325 | ||
| + | | Outdoor Unit Fan2 Motor Current Sensor SHORT / OPEN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 330 | ||
| + | | Outdoor plumbing inlet sensor out 0 time (TA_0) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 331 | ||
| + | | Outdoor sensor out once the entrance pipe (TA_1) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 332 | ||
| + | | 2, the inlet pipe outdoor sensor out (TA_2) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 333 | ||
| + | | Three times the inlet pipe outdoor sensor out (TA_3) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 334 | ||
| + | | Outdoor four times the inlet pipe sensor out (TA_4) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 335 | ||
| + | | Outdoor pipe exit sensor out 0 time (TB_0) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 336 | ||
| + | | 1 outdoor sensor out pipe outlet (TB_1) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 337 | ||
| + | | Outdoor sensor out two times pipe outlet (TB_2) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 338 | ||
| + | | Outdoor sensor out three times pipe outlet (TB_3) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 339 | ||
| + | | Outdoor sensor out four pipe outlet (TB_4) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 346 | ||
| + | | Error due to operation failure of Fan2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 347 | ||
| + | | Motor wire of Fan2 is not connected | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 348 | ||
| + | | Lock error on Fan2 of outdoor unit | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 353 | ||
| + | | Error due to overheated motor of outdoor unit’s Fan2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 355 | ||
| + | | Error due to overheated IPM of Fan2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 361 | ||
| + | | 2 CT1 inverter compressor start failure, or a low-current | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 364 | ||
| + | | Error due to over-current of inverter compressor 2. 2 DC Peak Inverter compressor stop | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 365 | ||
| + | | V-limit error of inverter compressor 2. 2 inverter compressor overload stops (30A or more) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 366 | ||
| + | | Error due to over voltage /low voltage of inverter PBA2. Less than 2 DC Link Voltage 150V 410V inverter over | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 367 | ||
| + | | Error due to unconnected wire of compressor 2. Inverter compressor rotation over 2 Wire dependence or compressor | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 368 | ||
| + | | Output current sensor error of inverter PBA2. 2 Comp inverter current sensor error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 369 | ||
| + | | DC voltage sensor error of inverter PBA2. 2 DC Link Inverter Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 371 | ||
| + | | 2 inverter outdoor unit EEPROM Read / Write error (OTP error) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 374 | ||
| + | | Heat sink temperature sensor error of inverter PBA2. 2 inverter heat sink temperature sensor error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 378 | ||
| + | | Hall IC connection error of Fan2. Outdoor fan 2 IPM H / W OC | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 385 | ||
| + | | Error due to input current of inverter 2. 2 inverter input current sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 386 | ||
| + | | Over-voltage/low-voltage error of Fan2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 387 | ||
| + | | Outdoor fan 2 Hall Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 389 | ||
| + | | V-limit error on Fan2 of compressor | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 391 | ||
| + | | Fan Controller 2 EEPROM Read / Write Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 393 | ||
| + | | Output current sensor error of Fan2. Fan Controller 2 Current sensor error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 396 | ||
| + | | DC voltage sensor error of Fan2. Fan Controller 2 DC Link sensor error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 399 | ||
| + | | Heat sink temperature sensor error of Fan2. 2 fan controller heat sink temperature sensor error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 400 | ||
| + | | Error due to overheat caused by contact failure on IPM of Inverter PBA2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 401 | ||
| + | | Outdoor Freezing detect 1 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 402 | ||
| + | | Outdoor Freezing detect 2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 403 | ||
| + | | Outdoor Freezing detect 3 - Freeze COMP DOWN | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 404 | ||
| + | | Outdoor overload 1 Protection Control Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 405 | ||
| + | | Outdoor overload 2 Protection Control Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 406 | ||
| + | | Outdoor overload 3 Protection Control Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 407 | ||
| + | | COMP down due to High PressureSensor Protection Control 1 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 408 | ||
| + | | COMP down due to High PressureSensor Protection Control 2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 409 | ||
| + | | COMP down due to High PressureSensor Protection Control 3 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 410 | ||
| + | | COMP down due to Low PressureSensor Protection Control 1 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 411 | ||
| + | | COMP down due to Low PressureSensor Protection Control 2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 412 | ||
| + | | COMP down due to Low PressureSensor Protection Control 3 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 413 | ||
| + | | Outdoor SUMP DOWN_1 Protection Control | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 414 | ||
| + | | Outdoor SUMP DOWN_2 Protection Control | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 415 | ||
| + | | Outdoor SUMP DOWN_3 Protection Control | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 416 | ||
| + | | Outdoor DischargeTemperature_1 Protection Control | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 417 | ||
| + | | Outdoor DischargeTemperature_2 Protection Control | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 418 | ||
| + | | Outdoor DischargeTemperature_3 Protection Control | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 419 | ||
| + | | Outdoor EEV#1 opening 6th Self-Check Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 420 | ||
| + | | Outdoor EEV#2 opening 6th Self-Check Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 421 | ||
| + | | Outdoor EEV#3 opening 6th Self-Check Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 422 | ||
| + | | Outdoor EEV#1 closing 6th Self-Check Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 423 | ||
| + | | Outdoor EEV#2 closing 6th Self-Check Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 424 | ||
| + | | Outdoor EEV#3 closing 6th Self-Check Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 425 | ||
| + | | Outdoor Reverse Phase or Missing Phase detect 1 Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 426 | ||
| + | | Outdoor Reverse Phase or Missing Phase detect 2 Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 427 | ||
| + | | Outdoor Reverse Phase or Missing Phase detect 3 Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 428 | ||
| + | | COMP down by Compression Ratio control Error 1 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 429 | ||
| + | | COMP down by Compression Ratio control Error 2 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 430 | ||
| + | | COMP down by Compression Ratio control Error 3 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 431 | ||
| + | | Oil Balance Valve1 Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 432 | ||
| + | | Oil Balance Valve2 Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 433 | ||
| + | | Oil Balance Valve3 Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 434 | ||
| + | | Oil Balance Valve opening Error (In DVM PLUS 2, HotGasValve Opening Error) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 435 | ||
| + | | Water Cooling Flow Switch Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 436 | ||
| + | | Evaporator Protect for Freeze and Burst Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 437 | ||
| + | | Oil Balance Valve Closing Error(In DVM PLUS 2, HotGasValve Opening Error) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 438 | ||
| + | | EVI EEV Opening Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 439 | ||
| + | | Error due to refrigerant leakage | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 440 | ||
| + | | Forbid Heat mode operation when outdoor temperature is over 30oC | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 441 | ||
| + | | Forbid Cooling Mode when OutdoorTemperature ia less than -5oC | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 442 | ||
| + | | Forbid an operation during heat mode with refrigerant charging operation when out door temperature | ||
| + | is over 15oC | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 443 | ||
| + | | Before Cooling working, less than Low Pressure 1K(inability to re-operate) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 445 | ||
| + | | CCH is detached. CCH Self-Check Error (CCH malfunction Or Sump Sensor miss connection) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 446 | ||
| + | | Error due to operation failure of Fan1. Fan Controller 1 Fan failed maneuver | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 447 | ||
| + | | Motor wire of Fan1 is not connected. Fan controller wiring 1 Wire U.S. | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 448 | ||
| + | | Lock error on Fan1. Fan Controller 1 Lock error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 450 | ||
| + | | COND High Temperature(Protection Control) Every Time | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 451 | ||
| + | | Low Pressure Switch Low Pressure(Protection Control) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 452 | ||
| + | | Instant power off Error (delete when COMP re-operate) | ||
| + | Outdoor Zero-Crossing Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 453 | ||
| + | | Outdoor Fan high temperaturet Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 454 | ||
| + | | OutdoorFan RPM Error (more than 2500rpm and the difference that target velocity compare with practical | ||
| + | velocity is more than 100rpm per 10SEC, more than 10 times) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 455 | ||
| + | | OutdoorFan IPM(Internal PCB Module) high temperature Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 456 | ||
| + | | OutdoorFan Overcurrent Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 457 | ||
| + | | OutdoorFan Reversed direction of the wind Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 458 | ||
| + | | Outdoor unit Fan (Fan Error) Or CT1 over currency | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 459 | ||
| + | | Outdoor unit IPM Fault Error Or CT2 over currency | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 460 | ||
| + | | Outdoor unit communication-power disconnected detect Or CT3 over currency | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 461 | ||
| + | | Inverter COMP operating failure Or CT1 low currency | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 462 | ||
| + | | All currency control COMP Stop Or CT2 low currency | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 463 | ||
| + | | OLP Temperature control COMP Stop Or CT3 low currency | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 464 | ||
| + | | DC Peak COMP stop | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 465 | ||
| + | | COMP Overload stop(over 30A) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 466 | ||
| + | | DC Link voltage less than 150V, over 410V | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 467 | ||
| + | | COMP revolute error Or COMP Wire In-connection | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 468 | ||
| + | | Inv Comp Current Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 469 | ||
| + | | DC Link Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 470 | ||
| + | | Outdoor unit EEPROM Read/Write Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 471 | ||
| + | | Outdoor unit EEPROM Read/Write Error(OTP error) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 472 | ||
| + | | Outdoor unit Zero crossing Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 473 | ||
| + | | Inverter Comp Lock Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 474 | ||
| + | | Heat sink temperature sensor error of inverter PBA1 | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 475 | ||
| + | | Outdoor unit BLDC Fan 2 Error Or | ||
| + | OutdoorFan2 RPM Error (more than 2500rpm and the difference that target velocity compare with practical | ||
| + | velocity is more than 100rpm per 10SEC, more than 10 times) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 476 | ||
| + | | 4wAY Error detect | ||
| + | | Self-Check, After 6 times, COMP DOWN | ||
| + | |- | ||
| + | | style="text-align: center; " | 477 | ||
| + | | Control for protecting liquid refrigerant | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 478 | ||
| + | | Error due to over current of Fan1. OutdoorFan IPM H/W OC | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 479 | ||
| + | | 4WAY miss connection detect Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 480 | ||
| + | | Fixed Comp 1 Stege OLP Protection Control(leakage for refrigerant Error) | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 481 | ||
| + | | Comp1 operating Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 482 | ||
| + | | Comp2 operating Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 483 | ||
| + | | Overvoltage of H/W Detect DC Link | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 484 | ||
| + | | PFC Overload (overcurrent) Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 485 | ||
| + | | Error due to input current of inverter 1. Input current Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 486 | ||
| + | | Error due to over voltage/low voltage of Fan. Outdoor Fan DC-Link Voltage Under/Over Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 487 | ||
| + | | Hall IC error of Fan1. Outdoor Fan Hall Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 489 | ||
| + | | V-limit error on Fan1 of compressor | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 490 | ||
| + | | Outdoor Temperature 0 degrees & Indoor Temperature less than 0 degrees prohibition to operate | ||
| + | | ERV Ventilation System | ||
| + | |- | ||
| + | | style="text-align: center; " | 491 | ||
| + | | Fan Controller1 EEPROM Read/Write Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 492 | ||
| + | | Outdoor Fan2 IPM H/W OC | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 493 | ||
| + | | Output current sensor error of Fan1. Fan Controller1 Current Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 494 | ||
| + | | Delayed time Error due to OutdoorFan2 Fan Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 495 | ||
| + | | Outdoor Fan2 Overheat Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 496 | ||
| + | | DC voltage sensor error of Fan1. Fan Controller1 DC Link Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 497 | ||
| + | | Outdoor Fan2 Overcurrent Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 498 | ||
| + | | Outdoor Fan2 IPM(Internal PCB Module) Overheat Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 499 | ||
| + | | Heat sink temperature sensor error of Fan1. Fan Controller1 Heat Sink Temp Sensor Error | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 500 | ||
| + | | IPM Overheat Error for Inverter COMP | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 505 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 506 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 507 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 508 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 509 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 510 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 505 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 506 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 507 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 508 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 509 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 510 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 505 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 506 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 507 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 508 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 509 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 510 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 505 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 506 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 507 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 508 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 509 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 510 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 505 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 506 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 507 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 508 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 509 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 510 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 505 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 506 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 507 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 508 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 509 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 510 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 505 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 506 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 507 | ||
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 508 |
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 509 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 510 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 501 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 502 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 503 | ||
| + | | | ||
| + | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 504 | ||
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 505 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 506 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 507 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 508 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 509 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 510 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 501 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 502 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 503 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 504 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 505 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 506 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 507 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 508 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 509 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 510 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 501 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 502 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 503 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 504 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 505 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 506 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 507 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 508 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 509 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 510 |
| | | | ||
| | | | ||
|- | |- | ||
Revision as of 05:04, 18 May 2019
Connection Diagrams
Samsung Self-diagnostic Malfunction (Error) Codes
| Malfunction Code |
Content of Abnormality | Notes |
|---|---|---|
| 101 | DVM,DPM,DVS:Outdoor Unit Communication Error (Indoor unit can’t receive communication) SINGLE: Indoor Unit Panel - Main communication error |
|
| 102 | Outdoor Unit to Indoor Unit communication error | |
| 103 | Communication Error Between Indoor Unit Panel and Main | |
| 104 | Communication Error | |
| 105 | Communication Error in between sensing space module and Indoor unit | |
| 106 | Communication Error Between LCD and Panel | |
| 107 | Communication Error Between LCD Outdoor Unit | |
| 108 | Error due to repeated address setting (When 2 or more devices has same address within the network) | |
| 109 | Communication error - indoor address is not completed. Check communication wire between indoor and
outdoor, outdoor unit quantity, indoor address setting status. |
|
| 121 | Error of ROOM Temperature Sensor in Indoor unit short/open | |
| 122 | Error of Evaporator_in Sensor of Indoor unit short/open | |
| 123 | Error of Evaporator_out Sensor of Indoor unit short/open | |
| 124 | Indoor Unit Communication Error (Indoor Unit /
Outdoor Unit Communication Error displayed in Outdoor unit) |
|
| 125 | Eva_mid2 Sensor of Indoor unit short/open | |
| 127 | Indoor Temperature (Suction Temperature) Sensor breakaway Error | |
| 128 | Breakaway of Indoor unit Evaporator_in Sensor | |
| 129 | Breakaway of Indoor unit Evaporator_out Sensor | |
| 130 | Breakaway of evaporator in and evaporator out sensors in indoor unit at the same time | |
| 131 | Sub(Electronic) Heater Sensor 1 Error | |
| 132 | Sub(Electronic) Heater Sensor 2 Error | |
| 133 | Sub(Electronic) Heater Sensor 3 Error | |
| 134 | Shutter Sensor Error (In case of model which have two shutter, upper Error : Aurora) | |
| 135 | Perfect Fan Sensor Error | |
| 136 | Shutter Sensor Error (In case, model which have two shutter Error in bottom : Aurora) | Aurora Bottom Sensor |
| 137 | VOC SENSOR OPEN/SHORT ERROR | |
| 138 | GAS SENSOR OPEN/SHORT ERROR | |
| 139 | ERV CO2 SENSOR OPEN/SHORT ERROR | |
| 140 | Indoor Dust sensor Error | |
| 141 | IAQ CO2 SENSOR OPEN/SHORT ERROR | |
| 142 | Indoor Unit Humid Sensor short/open | |
| 143 | Sensing space Sensor Error | |
| 144 | Eva2_in Sensor of Indoor Unit short/open | |
| 145 | Eva2_out Sensor of Indoor Unit short/open | |
| 146 | EEV Inlet Sensor short/open | |
| 147 | Indoor Eva2_in Sensor break away Error | |
| 148 | Indoor Eva2_out Sensor break away Error | |
| 149 | AHU Master Indoor room sensor setting error | |
| 150 | RESERVED(DMS-SNET3 Error) | |
| 151 | Open error of electoronic expansion valve in indoor unit(2nd) | Check MCU addressing if HR |
| 152 | Close error of electoronic expansion valve in indoor unit(2nd) | Check MCU addressing if HR |
| 153 | Dectect Indoor float s/w 2nd | |
| 154 | Indoor unit Fan Error | |
| 155 | Indoor unit Fan2 Error | |
| 156 | Indoor unit (EEV2) open error 2nd | |
| 157 | Indoor unit (EEV2) close error 2nd | |
| 158 | UDoor upper operation Error | (check Photo Sensor or operating Relay Error) |
| 159 | UDoor lower operation Error | (check Photo Sensor or operating Relay Error) |
| 161 | Cooling and Heating mixed operating Error | |
| 162 | Outdoor unit EEPROM error | |
| 163 | EEPROM OPTION SETTING ERROR | |
| 165 | Elect Discharge Temp Protect Error | |
| 166 | Electric motor related to no wind Error | |
| 167 | Unsing peripheral in Indoor Unit Option DIP S/W set Error | |
| 168 | IAQ Safety S/W Open Error | |
| 169 | AHU EEV Fault detection error | |
| 170 | Error; Fahrenheit /Celsius degree use same time (Indoor Unit which selected Celsius) | |
| 174 | ERV + heat exchanger inlet temperature sensor short / open | |
| 175 | Outdoor built-in indoor temperature sensor short / open error | |
| 177 | In hydro box, take place emergency signal Error | |
| 180 | MCU SOL Valve cooling/heating opening 1st at the same time | |
| 181 | MCU SOL Valve cooling/heating opening 1st at the same time | |
| 185 | Missconnect power line to Indoor Unit communication line | |
| 186 | sMPI(SPI) Feedback Error | |
| 187 | K1Filter Feedback Error | |
| 190 | While in checking pipe, no change Temp in Eva_in or change Temp Eva_in of other Indoor unit | |
| 191 | While in checking pipe, no change Temp in Eva_out or change Temp Eva_out of other Indoor unit | |
| 192 | Indoor Unit COVER OPEN (Indoor unit switch for safety) | |
| 193 | Indoor Panel Zero-Crossing Error | |
| 194 | Indoor Main Zero-Crossing Error | |
| 195 | IAQ safety S/W Open Error | |
| 198 | Error due to disconnected thermal fuse of indoor unit | |
| 199 | Error in Display Status of No pipe checking | |
| 201 | After complete Tracking 5 times, mismatch of the indoor unit quantity set with those
found by ODU error (some of indoor units disconnected communication wire, IDU powered off etc.) |
|
| 202 | System Down (All Indoor unit Short) due to Communication Error | |
| 203 | Outdoor Unit Communication Error Between MAIN-- SUB | |
| 204 | After completing Tracking 5 times, there is different with a number of set MCU and communicated MCU | |
| 205 | Communication Error on all PBA within the outdoor unit C-Box, communication cable error
Communication Error Between Outdoor Unit Inv Micom -- Fan Motor Micom |
|
| 206 | Communication Error Between Outdoor Unit Main PBA - Sub PBA | |
| 206-C001 | Communication Error Between Outdoor Unit Main PBA - Sub PBA | |
| 206-C002 | FAN PBA communication error | |
| 206-C003 | INV1 PBA communication error | |
| 206-C004 | INV2 PBA communication error | |
| 210 | Can NOT communicate with MCU over 2 min | |
| 211 | Indoor unit connected with confluence kit without continunity | |
| 212 | Indoor unit connected with confluence kit and setting address was overlapped more than 3 | |
| 213 | MCU address not matched with indoor unit address | |
| 214 | MCU address not matched with outdoor unit address | |
| 215 | Rotary switch for indoor unit address in MCU was over lapped among MCUs | |
| 216 | DIP switch for indoor unit setting was ON position even though indoor unit was not connected | |
| 217 | DIP switch for indoor unit setting was OFF position even though indoor unit was connected | |
| 218 | Setting number of indoor unit in MCU is larger than installed indoor units | |
| 219 | Error on temperature sensor located on MCU intercooler inlet (Short or Open)
MCU Over Cooling In Sensor Open/Short |
|
| 220 | Error on temperature sensor located on MCU intercooler outlet (Short or Open)
MCU Over Cooling Out Sensor Open/Short |
|
| 221 | OUT temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: more than 4.9V(-50oC), less than 0.4V(93oC) |
|
| 226 | OUT_temperature temperature Sensor breakaway Error | |
| 231 | COND_OUT Main temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC)” |
|
| 236 | COND_OUT Sub1 temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less 0.4V(93oC)” |
|
| 237 | COND temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC) |
|
| 241 | COND_MID or COND OUT Sensor of Outdoor Unit breakaway Error | |
| 242 | Outdoor Unit Heater Error | |
| 246 | COND_OUT 1 breakaway | |
| 251 | PWM DISCHARGE temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than -10oC - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) |
|
| 256 | Fixed COMP 1 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) |
|
| 257 | Fixed COMP 2 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C)” |
|
| 258 | Fixed COMP 3 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: Outdoor temperature more than -10 detect oC - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C) |
|
| 261 | Digital COMP_discharge Sensor breakaway Error | |
| 262 | Fixd COMP1_discharge Sensor breakaway Error | |
| 263 | Fixd COMP2_discharge Sensor breakaway Error | |
| 264 | Fixd COMP3_discharge Sensor breakaway Error | |
| 265 | SUMP temperature sensor breakaway (Main) | |
| 266 | SUMP temperature sensor breakaway (Sub1) | |
| 267 | High Pressure SENSOR breakaway ERROR | |
| 268 | SUMP temperature sensor breakaway (Sub3) | |
| 269 | SUCTION Sensor breakaway | |
| 271 | Digital COMP Sump_temperature Digital SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
| 276 | FIXED COMP1 Sump_temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
| 277 | FIXED COMP2 Sump_temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
| 278 | FIXED COMP3 Sump_temperature FIXED 3 SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C) |
|
| 291 | High pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect
(shortError: less than 0.4v, Error detect), (OPENError: over 4.2v, Error detect) |
|
| 296 | Low Pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect
(shortError: less than 0.4v, Error detect), (OPENError:over 4.7v, Error detect) |
|
| 301 | High Pressure SENSOR breakaway ERROR | |
| 306 | Low Pressure SENSOR breakaway ERROR | |
| 307 | Oil Balance Sensor SHORT/OPEN | |
| 308 | SUCTION Sensor SHORT/OPEN | |
| 309 | Oil Balace Sensor2 Sensor SHORT/OPEN | |
| 310 | Oil Balance Sensor3 Sensor SHORT/OPEN | |
| 311 | Double pipe Sensor SHORT/OPEN | |
| 312 | Main Cooling Sol Valve Open Error | |
| 313 | 4-Way Valve operation Error | |
| 314 | Oil Balace Sensor4 SHORT/OPEN | |
| 315 | CT1 Sensor Short or Open | |
| 316 | CT2 Sensor Short or Open | |
| 317 | CT3 Sensor Short or Open | |
| 320 | OLP Sensor SHORT / OPEN | |
| 321 | EVI INLET Sensor SHORT/OPEN | |
| 322 | EVI OUTLET Sensor SHORT/OPEN | |
| 323 | Error on suction sensor 2 (Short or Open) | |
| 324 | Outdoor Unit Fan Motor Current Sensor SHORT / OPEN | |
| 325 | Outdoor Unit Fan2 Motor Current Sensor SHORT / OPEN | |
| 330 | Outdoor plumbing inlet sensor out 0 time (TA_0) | |
| 331 | Outdoor sensor out once the entrance pipe (TA_1) | |
| 332 | 2, the inlet pipe outdoor sensor out (TA_2) | |
| 333 | Three times the inlet pipe outdoor sensor out (TA_3) | |
| 334 | Outdoor four times the inlet pipe sensor out (TA_4) | |
| 335 | Outdoor pipe exit sensor out 0 time (TB_0) | |
| 336 | 1 outdoor sensor out pipe outlet (TB_1) | |
| 337 | Outdoor sensor out two times pipe outlet (TB_2) | |
| 338 | Outdoor sensor out three times pipe outlet (TB_3) | |
| 339 | Outdoor sensor out four pipe outlet (TB_4) | |
| 346 | Error due to operation failure of Fan2 | |
| 347 | Motor wire of Fan2 is not connected | |
| 348 | Lock error on Fan2 of outdoor unit | |
| 353 | Error due to overheated motor of outdoor unit’s Fan2 | |
| 355 | Error due to overheated IPM of Fan2 | |
| 361 | 2 CT1 inverter compressor start failure, or a low-current | |
| 364 | Error due to over-current of inverter compressor 2. 2 DC Peak Inverter compressor stop | |
| 365 | V-limit error of inverter compressor 2. 2 inverter compressor overload stops (30A or more) | |
| 366 | Error due to over voltage /low voltage of inverter PBA2. Less than 2 DC Link Voltage 150V 410V inverter over | |
| 367 | Error due to unconnected wire of compressor 2. Inverter compressor rotation over 2 Wire dependence or compressor | |
| 368 | Output current sensor error of inverter PBA2. 2 Comp inverter current sensor error | |
| 369 | DC voltage sensor error of inverter PBA2. 2 DC Link Inverter Sensor Error | |
| 371 | 2 inverter outdoor unit EEPROM Read / Write error (OTP error) | |
| 374 | Heat sink temperature sensor error of inverter PBA2. 2 inverter heat sink temperature sensor error | |
| 378 | Hall IC connection error of Fan2. Outdoor fan 2 IPM H / W OC | |
| 385 | Error due to input current of inverter 2. 2 inverter input current sensor Error | |
| 386 | Over-voltage/low-voltage error of Fan2 | |
| 387 | Outdoor fan 2 Hall Sensor Error | |
| 389 | V-limit error on Fan2 of compressor | |
| 391 | Fan Controller 2 EEPROM Read / Write Error | |
| 393 | Output current sensor error of Fan2. Fan Controller 2 Current sensor error | |
| 396 | DC voltage sensor error of Fan2. Fan Controller 2 DC Link sensor error | |
| 399 | Heat sink temperature sensor error of Fan2. 2 fan controller heat sink temperature sensor error | |
| 400 | Error due to overheat caused by contact failure on IPM of Inverter PBA2 | |
| 401 | Outdoor Freezing detect 1 | |
| 402 | Outdoor Freezing detect 2 | |
| 403 | Outdoor Freezing detect 3 - Freeze COMP DOWN | |
| 404 | Outdoor overload 1 Protection Control Error | |
| 405 | Outdoor overload 2 Protection Control Error | |
| 406 | Outdoor overload 3 Protection Control Error | |
| 407 | COMP down due to High PressureSensor Protection Control 1 | |
| 408 | COMP down due to High PressureSensor Protection Control 2 | |
| 409 | COMP down due to High PressureSensor Protection Control 3 | |
| 410 | COMP down due to Low PressureSensor Protection Control 1 | |
| 411 | COMP down due to Low PressureSensor Protection Control 2 | |
| 412 | COMP down due to Low PressureSensor Protection Control 3 | |
| 413 | Outdoor SUMP DOWN_1 Protection Control | |
| 414 | Outdoor SUMP DOWN_2 Protection Control | |
| 415 | Outdoor SUMP DOWN_3 Protection Control | |
| 416 | Outdoor DischargeTemperature_1 Protection Control | |
| 417 | Outdoor DischargeTemperature_2 Protection Control | |
| 418 | Outdoor DischargeTemperature_3 Protection Control | |
| 419 | Outdoor EEV#1 opening 6th Self-Check Error | |
| 420 | Outdoor EEV#2 opening 6th Self-Check Error | |
| 421 | Outdoor EEV#3 opening 6th Self-Check Error | |
| 422 | Outdoor EEV#1 closing 6th Self-Check Error | |
| 423 | Outdoor EEV#2 closing 6th Self-Check Error | |
| 424 | Outdoor EEV#3 closing 6th Self-Check Error | |
| 425 | Outdoor Reverse Phase or Missing Phase detect 1 Error | |
| 426 | Outdoor Reverse Phase or Missing Phase detect 2 Error | |
| 427 | Outdoor Reverse Phase or Missing Phase detect 3 Error | |
| 428 | COMP down by Compression Ratio control Error 1 | |
| 429 | COMP down by Compression Ratio control Error 2 | |
| 430 | COMP down by Compression Ratio control Error 3 | |
| 431 | Oil Balance Valve1 Error | |
| 432 | Oil Balance Valve2 Error | |
| 433 | Oil Balance Valve3 Error | |
| 434 | Oil Balance Valve opening Error (In DVM PLUS 2, HotGasValve Opening Error) | |
| 435 | Water Cooling Flow Switch Error | |
| 436 | Evaporator Protect for Freeze and Burst Error | |
| 437 | Oil Balance Valve Closing Error(In DVM PLUS 2, HotGasValve Opening Error) | |
| 438 | EVI EEV Opening Error | |
| 439 | Error due to refrigerant leakage | |
| 440 | Forbid Heat mode operation when outdoor temperature is over 30oC | |
| 441 | Forbid Cooling Mode when OutdoorTemperature ia less than -5oC | |
| 442 | Forbid an operation during heat mode with refrigerant charging operation when out door temperature
is over 15oC |
|
| 443 | Before Cooling working, less than Low Pressure 1K(inability to re-operate) | |
| 445 | CCH is detached. CCH Self-Check Error (CCH malfunction Or Sump Sensor miss connection) | |
| 446 | Error due to operation failure of Fan1. Fan Controller 1 Fan failed maneuver | |
| 447 | Motor wire of Fan1 is not connected. Fan controller wiring 1 Wire U.S. | |
| 448 | Lock error on Fan1. Fan Controller 1 Lock error | |
| 450 | COND High Temperature(Protection Control) Every Time | |
| 451 | Low Pressure Switch Low Pressure(Protection Control) | |
| 452 | Instant power off Error (delete when COMP re-operate)
Outdoor Zero-Crossing Error |
|
| 453 | Outdoor Fan high temperaturet Error | |
| 454 | OutdoorFan RPM Error (more than 2500rpm and the difference that target velocity compare with practical
velocity is more than 100rpm per 10SEC, more than 10 times) |
|
| 455 | OutdoorFan IPM(Internal PCB Module) high temperature Error | |
| 456 | OutdoorFan Overcurrent Error | |
| 457 | OutdoorFan Reversed direction of the wind Error | |
| 458 | Outdoor unit Fan (Fan Error) Or CT1 over currency | |
| 459 | Outdoor unit IPM Fault Error Or CT2 over currency | |
| 460 | Outdoor unit communication-power disconnected detect Or CT3 over currency | |
| 461 | Inverter COMP operating failure Or CT1 low currency | |
| 462 | All currency control COMP Stop Or CT2 low currency | |
| 463 | OLP Temperature control COMP Stop Or CT3 low currency | |
| 464 | DC Peak COMP stop | |
| 465 | COMP Overload stop(over 30A) | |
| 466 | DC Link voltage less than 150V, over 410V | |
| 467 | COMP revolute error Or COMP Wire In-connection | |
| 468 | Inv Comp Current Sensor Error | |
| 469 | DC Link Sensor Error | |
| 470 | Outdoor unit EEPROM Read/Write Error | |
| 471 | Outdoor unit EEPROM Read/Write Error(OTP error) | |
| 472 | Outdoor unit Zero crossing Error | |
| 473 | Inverter Comp Lock Error | |
| 474 | Heat sink temperature sensor error of inverter PBA1 | |
| 475 | Outdoor unit BLDC Fan 2 Error Or
OutdoorFan2 RPM Error (more than 2500rpm and the difference that target velocity compare with practical velocity is more than 100rpm per 10SEC, more than 10 times) |
|
| 476 | 4wAY Error detect | Self-Check, After 6 times, COMP DOWN |
| 477 | Control for protecting liquid refrigerant | |
| 478 | Error due to over current of Fan1. OutdoorFan IPM H/W OC | |
| 479 | 4WAY miss connection detect Error | |
| 480 | Fixed Comp 1 Stege OLP Protection Control(leakage for refrigerant Error) | |
| 481 | Comp1 operating Error | |
| 482 | Comp2 operating Error | |
| 483 | Overvoltage of H/W Detect DC Link | |
| 484 | PFC Overload (overcurrent) Error | |
| 485 | Error due to input current of inverter 1. Input current Sensor Error | |
| 486 | Error due to over voltage/low voltage of Fan. Outdoor Fan DC-Link Voltage Under/Over Error | |
| 487 | Hall IC error of Fan1. Outdoor Fan Hall Sensor Error | |
| 489 | V-limit error on Fan1 of compressor | |
| 490 | Outdoor Temperature 0 degrees & Indoor Temperature less than 0 degrees prohibition to operate | ERV Ventilation System |
| 491 | Fan Controller1 EEPROM Read/Write Error | |
| 492 | Outdoor Fan2 IPM H/W OC | |
| 493 | Output current sensor error of Fan1. Fan Controller1 Current Sensor Error | |
| 494 | Delayed time Error due to OutdoorFan2 Fan Error | |
| 495 | Outdoor Fan2 Overheat Error | |
| 496 | DC voltage sensor error of Fan1. Fan Controller1 DC Link Sensor Error | |
| 497 | Outdoor Fan2 Overcurrent Error | |
| 498 | Outdoor Fan2 IPM(Internal PCB Module) Overheat Error | |
| 499 | Heat sink temperature sensor error of Fan1. Fan Controller1 Heat Sink Temp Sensor Error | |
| 500 | IPM Overheat Error for Inverter COMP | |
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 | ||
| 501 | ||
| 502 | ||
| 503 | ||
| 504 | ||
| 505 | ||
| 506 | ||
| 507 | ||
| 508 | ||
| 509 | ||
| 510 |