| Line 1,417: | Line 1,417: | ||
|- | |- | ||
| style="text-align: center; " | 801 | | style="text-align: center; " | 801 | ||
| − | | | + | | [GHP-R410A] communication error : “IF <-> Outdoor unit” : Disconnection |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 802 | | style="text-align: center; " | 802 | ||
| − | | | + | | [GHP-R410A] communication error : “Outdoor unit <-> IF” : Disconnection |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 803 | | style="text-align: center; " | 803 | ||
| − | | | + | | [GHP-R410A] communication error : “IF <-> Indoor unit” some disconnect in Indoor unit (communicating) |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 804 | | style="text-align: center; " | 804 | ||
| − | | | + | | [GHP-R410A] communication error : Among outdoor unit |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 805 | | style="text-align: center; " | 805 | ||
| − | | | + | | [GHP-R410A] Error setting outdoor unit organization |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 806 | | style="text-align: center; " | 806 | ||
| − | | | + | | [GHP-R410A] Remocon Sensor disconnect/short circuit |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 807 | | style="text-align: center; " | 807 | ||
| − | | | + | | [GHP-R410A] outdoor liquid pipe Sensor disconnect/short circuit |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 808 | | style="text-align: center; " | 808 | ||
| − | | | + | | [GHP-R410A] outdoor Unit - overcooling heat exchanger entry temp thermystor disconnect/short circuit |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 809 | | style="text-align: center; " | 809 | ||
| − | | | + | | [GHP-R410A]COMP suction temp overheat |
| | | | ||
|- | |- | ||
| style="text-align: center; " | 810 | | style="text-align: center; " | 810 | ||
| + | | [GHP-R410A] COMP suction superheat not soar | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 811 | ||
| + | | [GHP-R410A] refrigerant high pressure Switch disconnect | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 812 |
| + | | [GHP-R410A] Gas EEV Output error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 813 | ||
| + | | [GHP-R410A] refrigerant low pressure Sensor error(2nd) | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 814 |
| + | | [GHP-R410A] refrigerant high pressure Sensor error 1 | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 815 | ||
| + | | [GHP-R410A] refrigerant high pressure Sensor error 2 (value of high pressure sensor less | ||
| + | than standard low pressure) | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 816 |
| + | | [GHP-R410A] Water Pump operation failure | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 817 | ||
| + | | [GHP-R410A] Water Pump a number of revolute error | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 818 |
| + | | [GHP-R410A] IPM(outdoor unit FAN operating Driver) error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 819 | ||
| + | | [GHP-R410A] outdoor heat exchange Fan 1 operating failure | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 820 |
| + | | [GHP-R410A] outdoor heat exchange Fan 2 operating failure | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 821 | ||
| + | | [GHP-R410A] outdoor heat exchange Fan 3 operating failure | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 822 |
| + | | [GHP-R410A] outdoor heat exchange Fan 1 a number of revolute error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 823 | ||
| + | | [GHP-R410A] outdoor heat exchange Fan 2 a number of revolute error | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 824 |
| + | | [GHP-R410A] outdoor heat exchange Fan 3 a number of revolute error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 825 | ||
| + | | [GHP-R410A] outdoor Unit - heat exchange Fan error | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 826 |
| + | | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 1 disconnect/short circuit | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 827 | ||
| + | | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 2 disconnect/short circuit | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 828 |
| + | | [GHP-R410A] outdoor unit Unit - refrigerant low pressure Switch disconnect | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 829 | ||
| + | | [GHP-R410A] refrigerant low pressure error | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 830 |
| + | | [GHP-R410A] three phase error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 831 | ||
| + | | [GHP-R410A] one phase power part error | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 832 |
| + | | [GHP-R410A] Main - Sub MICOM Program Version Unmatch | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 833 | ||
| + | | [GHP-R410A] indoor unit connection number Over | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 834 |
| + | | [GHP-R410A] indoor unit connection capacity Over | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 835 | ||
| + | | [GHP-R410A] outdoor-indoor connection Unmatch | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 836 |
| + | | [GHP-R410A] Outdoor Unit -Regular Inspection | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 837 | ||
| + | | [GHP-R410A] Refrigerant High pressure error 1 | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 838 |
| + | | [GHP-R410A] Refrigerant High pressure error 2 | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 841 | ||
| + | | [GHP-R410A] Outdoor Unit Gas Temp Thermistor short/disconnection | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 843 |
| + | | [GHP-R410A] Engine water temp Sensor short/disconnection | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 844 | ||
| + | | [GHP-R410A] Engine discharge temp Sensor disconnection | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 845 |
| + | | [GHP-R410A] Engine fluid pressure error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 846 | ||
| + | | [GHP-R410A] Engine Fluid pressure Switch disconnected | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 847 |
| + | | [GHP-R410A] Engine over revolute 1 | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 848 | ||
| + | | [GHP-R410A] Engine over revolute 2 | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 849 |
| + | | [GHP-R410A] Starter Error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 850 | ||
| + | | [GHP-R410A] Engine a number of revolute control error | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 851 |
| + | | [GHP-R410A] Engine Stop | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 852 | ||
| + | | [GHP-R410A] IGUNAITA(firer) low voltage | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 853 |
| + | | [GHP-R410A] IGUNAITA(firer) disconnect | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 854 | ||
| + | | [GHP-R410A] IGUNAITA(firer) over voltage | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 855 |
| + | | [GHP-R410A] Engine discharge temp Error | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 856 | ||
| + | | [GHP-R410A] Engine water temp overheat | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 857 |
| + | | [GHP-R410A] Engine operation failure | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 858 | ||
| + | | [GHP-R410A] Engine cooling | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 859 |
| + | | [GHP-R410A] Engine insufficient operating revolute | ||
| | | | ||
| + | |- | ||
| + | | style="text-align: center; " | 860 | ||
| + | | [GHP-R410A] Engine a number of revolute Haunting Error | ||
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 861 |
| − | | | + | | [GHP-R410A] COMP discharge temperature overheat |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 862 |
| − | | | + | | [GHP-R410A] Compressor Discharge temperature Sensor1 short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 863 |
| − | | | + | | [GHP-R410A] Compressor Discharge temperature Sensor2 short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 864 |
| − | | | + | | [GHP-R410A] Compressor Discharge temperature Sensor3 short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 865 |
| − | | | + | | [GHP-R410A] Compressor Discharge temperature Sensor4 short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 866 |
| − | | | + | | [GHP-R410A] Compressor nhale temperature Sensor1 short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 867 |
| − | | | + | | [GHP-R410A] Compressor suction temperature Sensor2 short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 868 |
| − | | | + | | [GHP-R22] Outdoor Unit - Accum Entrance Temperature Sensor short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 869 |
| − | | | + | | [GHP-R22] Outdoor Unit - refrigerants Gas pipe temperature Sensor short/disconnection |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 870 |
| − | | | + | | [GHP-R22] Outdoor Unit - comp lubricating oil insufficiency error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 871 |
| − | | | + | | [GHP-R22] Outdoor Unit - Refrigerant overfill error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 872 |
| − | | | + | | [GHP-R22] Outdoor Unit - Compressor induction temperature error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 873 |
| − | | | + | | [GHP-R22] Engine cooling system Error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 874 |
| − | | | + | | [GHP-R22] Engine Oil System error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 875 |
| − | | | + | | [GHP-R22] Engine power system Error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 876 |
| − | | | + | | [GHP-R22] Engine operating/control system Error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 880 |
| − | | | + | | [GHP-R410A] Outdoor Unit - Engine Temp of Cooling water low |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 881 |
| − | | | + | | [GHP-R410A] Outdoor Unit - leakage of Engine oil |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 882 |
| − | | | + | | [GHP-R410A] Outdoor Unit - Lack of Comp oil |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 883 |
| − | | | + | | [GHP-R410A] Outdoor Unit - starter Trans voltage short |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 901 |
| − | | | + | | Water Inlet Sensor(Tw1) SHORT / OPEN |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 902 |
| − | | | + | | Water Outlet Sensor(Tw3) SHORT / OPEN |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 903 |
| − | | | + | | PHE Sensor(Tw2) SHORT / OPEN |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 904 |
| − | | | + | | Water TANK Sensor SHORT / OPEN |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 905 |
| − | | | + | | SOLAR Sensor SHORT / OPEN |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 911 |
| − | | | + | | Flow Swtich Open Error |
| | | | ||
|- | |- | ||
| − | | style="text-align: center; " | | + | | style="text-align: center; " | 912 |
| − | | | + | | Flow Swtich Close Error |
| | | | ||
|- | |- | ||
Latest revision as of 01:04, 19 May 2019
Connection Diagrams
Samsung Self-diagnostic Malfunction (Error) Codes
| Malfunction Code |
Content of Abnormality | Notes |
|---|---|---|
| 101 | DVM,DPM,DVS:Outdoor Unit Communication Error (Indoor unit can’t receive communication) SINGLE: Indoor Unit Panel - Main communication error |
|
| 102 | Outdoor Unit to Indoor Unit communication error | |
| 103 | Communication Error Between Indoor Unit Panel and Main | |
| 104 | Communication Error | |
| 105 | Communication Error in between sensing space module and Indoor unit | |
| 106 | Communication Error Between LCD and Panel | |
| 107 | Communication Error Between LCD Outdoor Unit | |
| 108 | Error due to repeated address setting (When 2 or more devices has same address within the network) | |
| 109 | Communication error - indoor address is not completed. Check communication wire between indoor and
outdoor, outdoor unit quantity, indoor address setting status. |
|
| 121 | Error of ROOM Temperature Sensor in Indoor unit short/open | |
| 122 | Error of Evaporator_in Sensor of Indoor unit short/open | |
| 123 | Error of Evaporator_out Sensor of Indoor unit short/open | |
| 124 | Indoor Unit Communication Error (Indoor Unit /
Outdoor Unit Communication Error displayed in Outdoor unit) |
|
| 125 | Eva_mid2 Sensor of Indoor unit short/open | |
| 127 | Indoor Temperature (Suction Temperature) Sensor breakaway Error | |
| 128 | Breakaway of Indoor unit Evaporator_in Sensor | |
| 129 | Breakaway of Indoor unit Evaporator_out Sensor | |
| 130 | Breakaway of evaporator in and evaporator out sensors in indoor unit at the same time | |
| 131 | Sub(Electronic) Heater Sensor 1 Error | |
| 132 | Sub(Electronic) Heater Sensor 2 Error | |
| 133 | Sub(Electronic) Heater Sensor 3 Error | |
| 134 | Shutter Sensor Error (In case of model which have two shutter, upper Error : Aurora) | |
| 135 | Perfect Fan Sensor Error | |
| 136 | Shutter Sensor Error (In case, model which have two shutter Error in bottom : Aurora) | Aurora Bottom Sensor |
| 137 | VOC SENSOR OPEN/SHORT ERROR | |
| 138 | GAS SENSOR OPEN/SHORT ERROR | |
| 139 | ERV CO2 SENSOR OPEN/SHORT ERROR | |
| 140 | Indoor Dust sensor Error | |
| 141 | IAQ CO2 SENSOR OPEN/SHORT ERROR | |
| 142 | Indoor Unit Humid Sensor short/open | |
| 143 | Sensing space Sensor Error | |
| 144 | Eva2_in Sensor of Indoor Unit short/open | |
| 145 | Eva2_out Sensor of Indoor Unit short/open | |
| 146 | EEV Inlet Sensor short/open | |
| 147 | Indoor Eva2_in Sensor break away Error | |
| 148 | Indoor Eva2_out Sensor break away Error | |
| 149 | AHU Master Indoor room sensor setting error | |
| 150 | RESERVED(DMS-SNET3 Error) | |
| 151 | Open error of electoronic expansion valve in indoor unit(2nd) | Check MCU addressing if HR |
| 152 | Close error of electoronic expansion valve in indoor unit(2nd) | Check MCU addressing if HR |
| 153 | Dectect Indoor float s/w 2nd | |
| 154 | Indoor unit Fan Error | |
| 155 | Indoor unit Fan2 Error | |
| 156 | Indoor unit (EEV2) open error 2nd | |
| 157 | Indoor unit (EEV2) close error 2nd | |
| 158 | UDoor upper operation Error | (check Photo Sensor or operating Relay Error) |
| 159 | UDoor lower operation Error | (check Photo Sensor or operating Relay Error) |
| 161 | Cooling and Heating mixed operating Error | |
| 162 | Outdoor unit EEPROM error | |
| 163 | EEPROM OPTION SETTING ERROR | |
| 165 | Elect Discharge Temp Protect Error | |
| 166 | Electric motor related to no wind Error | |
| 167 | Unsing peripheral in Indoor Unit Option DIP S/W set Error | |
| 168 | IAQ Safety S/W Open Error | |
| 169 | AHU EEV Fault detection error | |
| 170 | Error; Fahrenheit /Celsius degree use same time (Indoor Unit which selected Celsius) | |
| 174 | ERV + heat exchanger inlet temperature sensor short / open | |
| 175 | Outdoor built-in indoor temperature sensor short / open error | |
| 177 | In hydro box, take place emergency signal Error | |
| 180 | MCU SOL Valve cooling/heating opening 1st at the same time | |
| 181 | MCU SOL Valve cooling/heating opening 1st at the same time | |
| 185 | Missconnect power line to Indoor Unit communication line | |
| 186 | sMPI(SPI) Feedback Error | |
| 187 | K1Filter Feedback Error | |
| 190 | While in checking pipe, no change Temp in Eva_in or change Temp Eva_in of other Indoor unit | |
| 191 | While in checking pipe, no change Temp in Eva_out or change Temp Eva_out of other Indoor unit | |
| 192 | Indoor Unit COVER OPEN (Indoor unit switch for safety) | |
| 193 | Indoor Panel Zero-Crossing Error | |
| 194 | Indoor Main Zero-Crossing Error | |
| 195 | IAQ safety S/W Open Error | |
| 198 | Error due to disconnected thermal fuse of indoor unit | |
| 199 | Error in Display Status of No pipe checking | |
| 201 | After complete Tracking 5 times, mismatch of the indoor unit quantity set with those
found by ODU error (some of indoor units disconnected communication wire, IDU powered off etc.) |
|
| 202 | System Down (All Indoor unit Short) due to Communication Error | |
| 203 | Outdoor Unit Communication Error Between MAIN-- SUB | |
| 204 | After completing Tracking 5 times, there is different with a number of set MCU and communicated MCU | |
| 205 | Communication Error on all PBA within the outdoor unit C-Box, communication cable error
Communication Error Between Outdoor Unit Inv Micom -- Fan Motor Micom |
|
| 206 | Communication Error Between Outdoor Unit Main PBA - Sub PBA | |
| 206-C001 | Communication Error Between Outdoor Unit Main PBA - Sub PBA | |
| 206-C002 | FAN PBA communication error | |
| 206-C003 | INV1 PBA communication error | |
| 206-C004 | INV2 PBA communication error | |
| 210 | Can NOT communicate with MCU over 2 min | |
| 211 | Indoor unit connected with confluence kit without continunity | |
| 212 | Indoor unit connected with confluence kit and setting address was overlapped more than 3 | |
| 213 | MCU address not matched with indoor unit address | |
| 214 | MCU address not matched with outdoor unit address | |
| 215 | Rotary switch for indoor unit address in MCU was over lapped among MCUs | |
| 216 | DIP switch for indoor unit setting was ON position even though indoor unit was not connected | |
| 217 | DIP switch for indoor unit setting was OFF position even though indoor unit was connected | |
| 218 | Setting number of indoor unit in MCU is larger than installed indoor units | |
| 219 | Error on temperature sensor located on MCU intercooler inlet (Short or Open)
MCU Over Cooling In Sensor Open/Short |
|
| 220 | Error on temperature sensor located on MCU intercooler outlet (Short or Open)
MCU Over Cooling Out Sensor Open/Short |
|
| 221 | OUT temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: more than 4.9V(-50oC), less than 0.4V(93oC) |
|
| 226 | OUT_temperature temperature Sensor breakaway Error | |
| 231 | COND_OUT Main temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC)” |
|
| 236 | COND_OUT Sub1 temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less 0.4V(93oC)” |
|
| 237 | COND temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC) |
|
| 241 | COND_MID or COND OUT Sensor of Outdoor Unit breakaway Error | |
| 242 | Outdoor Unit Heater Error | |
| 246 | COND_OUT 1 breakaway | |
| 251 | PWM DISCHARGE temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than -10oC - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) |
|
| 256 | Fixed COMP 1 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) |
|
| 257 | Fixed COMP 2 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C)” |
|
| 258 | Fixed COMP 3 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: Outdoor temperature more than -10 detect oC - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C) |
|
| 261 | Digital COMP_discharge Sensor breakaway Error | |
| 262 | Fixd COMP1_discharge Sensor breakaway Error | |
| 263 | Fixd COMP2_discharge Sensor breakaway Error | |
| 264 | Fixd COMP3_discharge Sensor breakaway Error | |
| 265 | SUMP temperature sensor breakaway (Main) | |
| 266 | SUMP temperature sensor breakaway (Sub1) | |
| 267 | High Pressure SENSOR breakaway ERROR | |
| 268 | SUMP temperature sensor breakaway (Sub3) | |
| 269 | SUCTION Sensor breakaway | |
| 271 | Digital COMP Sump_temperature Digital SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
| 276 | FIXED COMP1 Sump_temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
| 277 | FIXED COMP2 Sump_temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
| 278 | FIXED COMP3 Sump_temperature FIXED 3 SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C) |
|
| 291 | High pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect
(shortError: less than 0.4v, Error detect), (OPENError: over 4.2v, Error detect) |
|
| 296 | Low Pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect
(shortError: less than 0.4v, Error detect), (OPENError:over 4.7v, Error detect) |
|
| 301 | High Pressure SENSOR breakaway ERROR | |
| 306 | Low Pressure SENSOR breakaway ERROR | |
| 307 | Oil Balance Sensor SHORT/OPEN | |
| 308 | SUCTION Sensor SHORT/OPEN | |
| 309 | Oil Balace Sensor2 Sensor SHORT/OPEN | |
| 310 | Oil Balance Sensor3 Sensor SHORT/OPEN | |
| 311 | Double pipe Sensor SHORT/OPEN | |
| 312 | Main Cooling Sol Valve Open Error | |
| 313 | 4-Way Valve operation Error | |
| 314 | Oil Balace Sensor4 SHORT/OPEN | |
| 315 | CT1 Sensor Short or Open | |
| 316 | CT2 Sensor Short or Open | |
| 317 | CT3 Sensor Short or Open | |
| 320 | OLP Sensor SHORT / OPEN | |
| 321 | EVI INLET Sensor SHORT/OPEN | |
| 322 | EVI OUTLET Sensor SHORT/OPEN | |
| 323 | Error on suction sensor 2 (Short or Open) | |
| 324 | Outdoor Unit Fan Motor Current Sensor SHORT / OPEN | |
| 325 | Outdoor Unit Fan2 Motor Current Sensor SHORT / OPEN | |
| 330 | Outdoor plumbing inlet sensor out 0 time (TA_0) | |
| 331 | Outdoor sensor out once the entrance pipe (TA_1) | |
| 332 | 2, the inlet pipe outdoor sensor out (TA_2) | |
| 333 | Three times the inlet pipe outdoor sensor out (TA_3) | |
| 334 | Outdoor four times the inlet pipe sensor out (TA_4) | |
| 335 | Outdoor pipe exit sensor out 0 time (TB_0) | |
| 336 | 1 outdoor sensor out pipe outlet (TB_1) | |
| 337 | Outdoor sensor out two times pipe outlet (TB_2) | |
| 338 | Outdoor sensor out three times pipe outlet (TB_3) | |
| 339 | Outdoor sensor out four pipe outlet (TB_4) | |
| 346 | Error due to operation failure of Fan2 | |
| 347 | Motor wire of Fan2 is not connected | |
| 348 | Lock error on Fan2 of outdoor unit | |
| 353 | Error due to overheated motor of outdoor unit’s Fan2 | |
| 355 | Error due to overheated IPM of Fan2 | |
| 361 | 2 CT1 inverter compressor start failure, or a low-current | |
| 364 | Error due to over-current of inverter compressor 2. 2 DC Peak Inverter compressor stop | |
| 365 | V-limit error of inverter compressor 2. 2 inverter compressor overload stops (30A or more) | |
| 366 | Error due to over voltage /low voltage of inverter PBA2. Less than 2 DC Link Voltage 150V 410V inverter over | |
| 367 | Error due to unconnected wire of compressor 2. Inverter compressor rotation over 2 Wire dependence or compressor | |
| 368 | Output current sensor error of inverter PBA2. 2 Comp inverter current sensor error | |
| 369 | DC voltage sensor error of inverter PBA2. 2 DC Link Inverter Sensor Error | |
| 371 | 2 inverter outdoor unit EEPROM Read / Write error (OTP error) | |
| 374 | Heat sink temperature sensor error of inverter PBA2. 2 inverter heat sink temperature sensor error | |
| 378 | Hall IC connection error of Fan2. Outdoor fan 2 IPM H / W OC | |
| 385 | Error due to input current of inverter 2. 2 inverter input current sensor Error | |
| 386 | Over-voltage/low-voltage error of Fan2 | |
| 387 | Outdoor fan 2 Hall Sensor Error | |
| 389 | V-limit error on Fan2 of compressor | |
| 391 | Fan Controller 2 EEPROM Read / Write Error | |
| 393 | Output current sensor error of Fan2. Fan Controller 2 Current sensor error | |
| 396 | DC voltage sensor error of Fan2. Fan Controller 2 DC Link sensor error | |
| 399 | Heat sink temperature sensor error of Fan2. 2 fan controller heat sink temperature sensor error | |
| 400 | Error due to overheat caused by contact failure on IPM of Inverter PBA2 | |
| 401 | Outdoor Freezing detect 1 | |
| 402 | Outdoor Freezing detect 2 | |
| 403 | Outdoor Freezing detect 3 - Freeze COMP DOWN | |
| 404 | Outdoor overload 1 Protection Control Error | |
| 405 | Outdoor overload 2 Protection Control Error | |
| 406 | Outdoor overload 3 Protection Control Error | |
| 407 | COMP down due to High PressureSensor Protection Control 1 | |
| 408 | COMP down due to High PressureSensor Protection Control 2 | |
| 409 | COMP down due to High PressureSensor Protection Control 3 | |
| 410 | COMP down due to Low PressureSensor Protection Control 1 | |
| 411 | COMP down due to Low PressureSensor Protection Control 2 | |
| 412 | COMP down due to Low PressureSensor Protection Control 3 | |
| 413 | Outdoor SUMP DOWN_1 Protection Control | |
| 414 | Outdoor SUMP DOWN_2 Protection Control | |
| 415 | Outdoor SUMP DOWN_3 Protection Control | |
| 416 | Outdoor DischargeTemperature_1 Protection Control | |
| 417 | Outdoor DischargeTemperature_2 Protection Control | |
| 418 | Outdoor DischargeTemperature_3 Protection Control | |
| 419 | Outdoor EEV#1 opening 6th Self-Check Error | |
| 420 | Outdoor EEV#2 opening 6th Self-Check Error | |
| 421 | Outdoor EEV#3 opening 6th Self-Check Error | |
| 422 | Outdoor EEV#1 closing 6th Self-Check Error | |
| 423 | Outdoor EEV#2 closing 6th Self-Check Error | |
| 424 | Outdoor EEV#3 closing 6th Self-Check Error | |
| 425 | Outdoor Reverse Phase or Missing Phase detect 1 Error | |
| 426 | Outdoor Reverse Phase or Missing Phase detect 2 Error | |
| 427 | Outdoor Reverse Phase or Missing Phase detect 3 Error | |
| 428 | COMP down by Compression Ratio control Error 1 | |
| 429 | COMP down by Compression Ratio control Error 2 | |
| 430 | COMP down by Compression Ratio control Error 3 | |
| 431 | Oil Balance Valve1 Error | |
| 432 | Oil Balance Valve2 Error | |
| 433 | Oil Balance Valve3 Error | |
| 434 | Oil Balance Valve opening Error (In DVM PLUS 2, HotGasValve Opening Error) | |
| 435 | Water Cooling Flow Switch Error | |
| 436 | Evaporator Protect for Freeze and Burst Error | |
| 437 | Oil Balance Valve Closing Error(In DVM PLUS 2, HotGasValve Opening Error) | |
| 438 | EVI EEV Opening Error | |
| 439 | Error due to refrigerant leakage | |
| 440 | Forbid Heat mode operation when outdoor temperature is over 30oC | |
| 441 | Forbid Cooling Mode when OutdoorTemperature ia less than -5oC | |
| 442 | Forbid an operation during heat mode with refrigerant charging operation when out door temperature
is over 15oC |
|
| 443 | Before Cooling working, less than Low Pressure 1K(inability to re-operate) | |
| 445 | CCH is detached. CCH Self-Check Error (CCH malfunction Or Sump Sensor miss connection) | |
| 446 | Error due to operation failure of Fan1. Fan Controller 1 Fan failed maneuver | |
| 447 | Motor wire of Fan1 is not connected. Fan controller wiring 1 Wire U.S. | |
| 448 | Lock error on Fan1. Fan Controller 1 Lock error | |
| 450 | COND High Temperature(Protection Control) Every Time | |
| 451 | Low Pressure Switch Low Pressure(Protection Control) | |
| 452 | Instant power off Error (delete when COMP re-operate)
Outdoor Zero-Crossing Error |
|
| 453 | Outdoor Fan high temperaturet Error | |
| 454 | OutdoorFan RPM Error (more than 2500rpm and the difference that target velocity compare with practical
velocity is more than 100rpm per 10SEC, more than 10 times) |
|
| 455 | OutdoorFan IPM(Internal PCB Module) high temperature Error | |
| 456 | OutdoorFan Overcurrent Error | |
| 457 | OutdoorFan Reversed direction of the wind Error | |
| 458 | Outdoor unit Fan (Fan Error) Or CT1 over currency | |
| 459 | Outdoor unit IPM Fault Error Or CT2 over currency | |
| 460 | Outdoor unit communication-power disconnected detect Or CT3 over currency | |
| 461 | Inverter COMP operating failure Or CT1 low currency | |
| 462 | All currency control COMP Stop Or CT2 low currency | |
| 463 | OLP Temperature control COMP Stop Or CT3 low currency | |
| 464 | DC Peak COMP stop | |
| 465 | COMP Overload stop(over 30A) | |
| 466 | DC Link voltage less than 150V, over 410V | |
| 467 | COMP revolute error Or COMP Wire In-connection | |
| 468 | Inv Comp Current Sensor Error | |
| 469 | DC Link Sensor Error | |
| 470 | Outdoor unit EEPROM Read/Write Error | |
| 471 | Outdoor unit EEPROM Read/Write Error(OTP error) | |
| 472 | Outdoor unit Zero crossing Error | |
| 473 | Inverter Comp Lock Error | |
| 474 | Heat sink temperature sensor error of inverter PBA1 | |
| 475 | Outdoor unit BLDC Fan 2 Error Or
OutdoorFan2 RPM Error (more than 2500rpm and the difference that target velocity compare with practical velocity is more than 100rpm per 10SEC, more than 10 times) |
|
| 476 | 4wAY Error detect | Self-Check, After 6 times, COMP DOWN |
| 477 | Control for protecting liquid refrigerant | |
| 478 | Error due to over current of Fan1. OutdoorFan IPM H/W OC | |
| 479 | 4WAY miss connection detect Error | |
| 480 | Fixed Comp 1 Stege OLP Protection Control(leakage for refrigerant Error) | |
| 481 | Comp1 operating Error | |
| 482 | Comp2 operating Error | |
| 483 | Overvoltage of H/W Detect DC Link | |
| 484 | PFC Overload (overcurrent) Error | |
| 485 | Error due to input current of inverter 1. Input current Sensor Error | |
| 486 | Error due to over voltage/low voltage of Fan. Outdoor Fan DC-Link Voltage Under/Over Error | |
| 487 | Hall IC error of Fan1. Outdoor Fan Hall Sensor Error | |
| 489 | V-limit error on Fan1 of compressor | |
| 490 | Outdoor Temperature 0 degrees & Indoor Temperature less than 0 degrees prohibition to operate | ERV Ventilation System |
| 491 | Fan Controller1 EEPROM Read/Write Error | |
| 492 | Outdoor Fan2 IPM H/W OC | |
| 493 | Output current sensor error of Fan1. Fan Controller1 Current Sensor Error | |
| 494 | Delayed time Error due to OutdoorFan2 Fan Error | |
| 495 | Outdoor Fan2 Overheat Error | |
| 496 | DC voltage sensor error of Fan1. Fan Controller1 DC Link Sensor Error | |
| 497 | Outdoor Fan2 Overcurrent Error | |
| 498 | Outdoor Fan2 IPM(Internal PCB Module) Overheat Error | |
| 499 | Heat sink temperature sensor error of Fan1. Fan Controller1 Heat Sink Temp Sensor Error | |
| 500 | IPM Overheat Error for Inverter COMP | |
| 503 | Error due to alert the user to check if the service valve is closed | |
| 504 | Error due to self diagnosis of compressor operation | |
| 505 | Error due to self diagnosis of high pressure sensor | |
| 506 | Error due to self diagnosis of low pressure sensor | |
| 512 | RESERVED(DMS-SNET3 Error) | |
| 551 | Defrost working | |
| 552 | Low Discharge Pressure | |
| 553 | Equability operation | |
| 554 | loading_failure / total Leakage of Refrigerant of Outdoor Unit | |
| 555 | Recovery of oil | |
| 556 | Outdoor Unit power set option Error | |
| 557 | When DPM mode, Product option are not same between indoor units | |
| 559 | Indoor Unit operating stop due to detect unknown error in Outdoor Unit | |
| 560 | Outdoor Unit Switch option setting error(not applied) | |
| 561 | Outdoor Unit SA(SUPPLY AIR) FAN RPM | |
| 562 | Outdoor Unit RA(ROOM AIR) FAN RPM | |
| 563 | Indoor Unit mixed install error | |
| 564 | IAQ Clean Fan Error | |
| 565 | Miss connection Error between Comp and power wire - power line of Eva1 connect with Comp2 or
power line of Eva2 connect with Comp1 |
|
| 570 | Boot Code Check FAIL | |
| 573 | Error due to using single type outdoor unit in a module installation | |
| 574 | Total Leakage of Refrigerant of Outdoor Unit 2 | |
| 575 | Total Leakage of Refrigerant of Outdoor Unit 3 (Comp1, Comp2 bot detected) | |
| 601 | Wired LCD (controller) <-> Indoor Unit Communication Error | |
| 602 | Master Wire LCD <-> Slave Wire LCD Communication Error | |
| 603 | Communication Packet Error (Baudrate / different communication type) | |
| 604 | Wired LCD (controller) <-> Indoor Unit Tracking Error over 10 times | |
| 605 | 7 Day Scheduler <-> Wire LCD ,CAUR Communication Error | |
| 606 | Wire LCD COM1/COM2 Cross Install Error | |
| 607 | Wile Wire LCD Master-Master installation, Communication Error | |
| 608 | External linkage ERV Controller No installation Error | |
| 609 | External linkage Indoor No installation Error | |
| 610 | CAUR <-> Transmitter Communication Error | |
| 611 | DMS <-> CAUR Communication Error | |
| 612 | DMS <-> PEAK Transmitter Communication Error | |
| 613 | DMS <-> PIM/SIM Transmitter Communication Error | |
| 614 | Amount of electricity system <-> PIM/SIM Transmitter Communication Error | |
| 615 | Transmitter <-> Indoor unit Communication Error (After complete Transmitter Tracking, for 2min some indoor
unit can’t communicate.) |
|
| 616 | Transmitter <-> Outdoor unit Communication Error (After completeTransmitter Tracking, for 2min outdoor
unit can’t communicate) |
|
| 617 | Peak power Transmitter <-> Demand Controller Communication Error, Demand Transmitter
<-> Amount of eletricity system communication Error |
|
| 618 | ERV Controller+indoor unit (16EA) over Max install number Error | |
| 619 | Celcius/Fahrenheit indoor unit mixed install error | |
| 620 | New wired remote controller "Celcius/Fahrenheit" set error (DIP S/W #4 set error) | |
| 621 | New Wire Remote controller Master/Slave Dip Switch option Set Error (Difference with set option of
Master and Slave) |
|
| 622 | Demand Controller / select the type of amount of electricity system Error | |
| 623 | Demand Transmitter PT / CT ratio set Error | |
| 624 | Demand Transmitter data receive error from amount of electricity | |
| 625 | Master DMS ? Slave DMS Communication Error | |
| 626 | ERV linkage wire remote controller(AWR-WE00) ERV separate installation Error (not connect indoor unit
and, only ERV be installed) indoor unit linkage wire remocontroller(AWR-VH10) indoor unit separate installation Error (not connect indoor unit and, only ERV be installed) |
|
| 627 | While in linkage controll Master/Slave Wire Remote controller, Slave Wire Remote controller 2EA installation
Error (Installing Wire Remocontroller set slave in Master Wire Remocontroller 2EA at the same time) |
|
| 628 | DMS <-> Transmitter Communication Error | |
| 629 | DMS <-> DDC Communication Error | |
| 630 | ERV wire remote controller normal ventilation option set Error
- Check normal ventilation option set only. - ERV normal ventilation No option, use Wire Remote controller option normal ventilation |
|
| 631 | ERVWire Remote controller auto ventilation option set Error
- Check set auto ventilation only - ERV auto ventilation no option, use wire remote controller auto ventilation |
|
| 632 | Error when input the pulse except set the value of Pulse Width by PIM
1. less than 20ms , 2. over 400ms , 3. over range of set pulse width, 4. repeated purse over 3min |
|
| 652 | While COM 1 Dual Master installation Commnunication Error | |
| 653 | Temperature Sensor Open/Short Error | |
| 654 | FRAM Error or damper Error(ERV model) | |
| 655 | RESERVED(DMS-SNET3 Error) | |
| 656 | RESERVED(DMS-SNET3 Error) | |
| 701 | Float 1st | |
| 702 | Indoor EEV clsosing 1st | |
| 703 | Indoor EEV opening 1st | |
| 720 | Outdoor EEV#1 opening Self-Check Every time error | |
| 721 | Outdoor EEV#2 opening Self-Check Every time error | |
| 722 | Outdoor EEV#3 opening Self-Check Every time error | |
| 723 | Outdoor EEV#1 closing Self-Check Every time error | |
| 724 | Outdoor EEV#2 closing Self-Check Every time error | |
| 725 | Outdoor EEV#3 closing Self-Check Every time error | |
| 768 | RESERVED(DMS-SNET3) | |
| 801 | [GHP-R410A] communication error : “IF <-> Outdoor unit” : Disconnection | |
| 802 | [GHP-R410A] communication error : “Outdoor unit <-> IF” : Disconnection | |
| 803 | [GHP-R410A] communication error : “IF <-> Indoor unit” some disconnect in Indoor unit (communicating) | |
| 804 | [GHP-R410A] communication error : Among outdoor unit | |
| 805 | [GHP-R410A] Error setting outdoor unit organization | |
| 806 | [GHP-R410A] Remocon Sensor disconnect/short circuit | |
| 807 | [GHP-R410A] outdoor liquid pipe Sensor disconnect/short circuit | |
| 808 | [GHP-R410A] outdoor Unit - overcooling heat exchanger entry temp thermystor disconnect/short circuit | |
| 809 | [GHP-R410A]COMP suction temp overheat | |
| 810 | [GHP-R410A] COMP suction superheat not soar | |
| 811 | [GHP-R410A] refrigerant high pressure Switch disconnect | |
| 812 | [GHP-R410A] Gas EEV Output error | |
| 813 | [GHP-R410A] refrigerant low pressure Sensor error(2nd) | |
| 814 | [GHP-R410A] refrigerant high pressure Sensor error 1 | |
| 815 | [GHP-R410A] refrigerant high pressure Sensor error 2 (value of high pressure sensor less
than standard low pressure) |
|
| 816 | [GHP-R410A] Water Pump operation failure | |
| 817 | [GHP-R410A] Water Pump a number of revolute error | |
| 818 | [GHP-R410A] IPM(outdoor unit FAN operating Driver) error | |
| 819 | [GHP-R410A] outdoor heat exchange Fan 1 operating failure | |
| 820 | [GHP-R410A] outdoor heat exchange Fan 2 operating failure | |
| 821 | [GHP-R410A] outdoor heat exchange Fan 3 operating failure | |
| 822 | [GHP-R410A] outdoor heat exchange Fan 1 a number of revolute error | |
| 823 | [GHP-R410A] outdoor heat exchange Fan 2 a number of revolute error | |
| 824 | [GHP-R410A] outdoor heat exchange Fan 3 a number of revolute error | |
| 825 | [GHP-R410A] outdoor Unit - heat exchange Fan error | |
| 826 | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 1 disconnect/short circuit | |
| 827 | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 2 disconnect/short circuit | |
| 828 | [GHP-R410A] outdoor unit Unit - refrigerant low pressure Switch disconnect | |
| 829 | [GHP-R410A] refrigerant low pressure error | |
| 830 | [GHP-R410A] three phase error | |
| 831 | [GHP-R410A] one phase power part error | |
| 832 | [GHP-R410A] Main - Sub MICOM Program Version Unmatch | |
| 833 | [GHP-R410A] indoor unit connection number Over | |
| 834 | [GHP-R410A] indoor unit connection capacity Over | |
| 835 | [GHP-R410A] outdoor-indoor connection Unmatch | |
| 836 | [GHP-R410A] Outdoor Unit -Regular Inspection | |
| 837 | [GHP-R410A] Refrigerant High pressure error 1 | |
| 838 | [GHP-R410A] Refrigerant High pressure error 2 | |
| 841 | [GHP-R410A] Outdoor Unit Gas Temp Thermistor short/disconnection | |
| 843 | [GHP-R410A] Engine water temp Sensor short/disconnection | |
| 844 | [GHP-R410A] Engine discharge temp Sensor disconnection | |
| 845 | [GHP-R410A] Engine fluid pressure error | |
| 846 | [GHP-R410A] Engine Fluid pressure Switch disconnected | |
| 847 | [GHP-R410A] Engine over revolute 1 | |
| 848 | [GHP-R410A] Engine over revolute 2 | |
| 849 | [GHP-R410A] Starter Error | |
| 850 | [GHP-R410A] Engine a number of revolute control error | |
| 851 | [GHP-R410A] Engine Stop | |
| 852 | [GHP-R410A] IGUNAITA(firer) low voltage | |
| 853 | [GHP-R410A] IGUNAITA(firer) disconnect | |
| 854 | [GHP-R410A] IGUNAITA(firer) over voltage | |
| 855 | [GHP-R410A] Engine discharge temp Error | |
| 856 | [GHP-R410A] Engine water temp overheat | |
| 857 | [GHP-R410A] Engine operation failure | |
| 858 | [GHP-R410A] Engine cooling | |
| 859 | [GHP-R410A] Engine insufficient operating revolute | |
| 860 | [GHP-R410A] Engine a number of revolute Haunting Error | |
| 861 | [GHP-R410A] COMP discharge temperature overheat | |
| 862 | [GHP-R410A] Compressor Discharge temperature Sensor1 short/disconnection | |
| 863 | [GHP-R410A] Compressor Discharge temperature Sensor2 short/disconnection | |
| 864 | [GHP-R410A] Compressor Discharge temperature Sensor3 short/disconnection | |
| 865 | [GHP-R410A] Compressor Discharge temperature Sensor4 short/disconnection | |
| 866 | [GHP-R410A] Compressor nhale temperature Sensor1 short/disconnection | |
| 867 | [GHP-R410A] Compressor suction temperature Sensor2 short/disconnection | |
| 868 | [GHP-R22] Outdoor Unit - Accum Entrance Temperature Sensor short/disconnection | |
| 869 | [GHP-R22] Outdoor Unit - refrigerants Gas pipe temperature Sensor short/disconnection | |
| 870 | [GHP-R22] Outdoor Unit - comp lubricating oil insufficiency error | |
| 871 | [GHP-R22] Outdoor Unit - Refrigerant overfill error | |
| 872 | [GHP-R22] Outdoor Unit - Compressor induction temperature error | |
| 873 | [GHP-R22] Engine cooling system Error | |
| 874 | [GHP-R22] Engine Oil System error | |
| 875 | [GHP-R22] Engine power system Error | |
| 876 | [GHP-R22] Engine operating/control system Error | |
| 880 | [GHP-R410A] Outdoor Unit - Engine Temp of Cooling water low | |
| 881 | [GHP-R410A] Outdoor Unit - leakage of Engine oil | |
| 882 | [GHP-R410A] Outdoor Unit - Lack of Comp oil | |
| 883 | [GHP-R410A] Outdoor Unit - starter Trans voltage short | |
| 901 | Water Inlet Sensor(Tw1) SHORT / OPEN | |
| 902 | Water Outlet Sensor(Tw3) SHORT / OPEN | |
| 903 | PHE Sensor(Tw2) SHORT / OPEN | |
| 904 | Water TANK Sensor SHORT / OPEN | |
| 905 | SOLAR Sensor SHORT / OPEN | |
| 911 | Flow Swtich Open Error | |
| 912 | Flow Swtich Close Error |