To enable proper Auto mode control from CoolMasterNet of the Indoor Unit connected via KRP928A2S adapter, make sure to configure SW3 switch to GLO position: 
 +
[[File:KRP928A2S-SW3.png]]
  
 
== Daikin Self-diagnostic Malfunction (Error) Codes ==
 
== Daikin Self-diagnostic Malfunction (Error) Codes ==

Revision as of 01:04, 7 August 2016

Setting Indoor Group Address

Indoor Group Address is required for proper CoolMasterNet operation. Without Group Address Indoor unit is not visible and can not be controlled by CoolMasterNet. Group Address is set with wired remote controller. Here is a simple sequence of operations for Daikin BRCE61 wired remote controller to set Group Address.

  • Press and hold Cancel button for a few seconds

BRC1E61-buttons.gif

  • Scroll down to Group No. setting function and press Menu/Enter button

BRC1E61-group-address-menu.gif

  • Program Group Address and then press Menu/Enter to save address

Remember if Indoor unit can not see a CoolMasterNet you won't have the Group Address menu option. So make sure the CoolMasterNet is wired to F1 F2 HVAC line and powered.

KRP928A2S Autom Mode Control

To enable proper Auto mode control from CoolMasterNet of the Indoor Unit connected via KRP928A2S adapter, make sure to configure SW3 switch to GLO position: KRP928A2S-SW3.png

Daikin Self-diagnostic Malfunction (Error) Codes

I
n
d
o
o
r

U
n
i
t
Malfunction

Code

Problem

Description

Supposed

Causes

Models
RA Sky
Air
VRV Pac
kage
HRV Chil
ler
Fan
Coil
A0 External protection device activated External protection device connected to the terminal strip T1-T2 of indoor unit is activated V V V
A1 Malfunction of indoor unit PCB Defective indoor unit PCB
External factor (Noise etc.)
V V V V V V
A3 Drain Level Control System Abnormality Drain clogging, upward slope, etc
Defective drain pump
Defective float switch or short circuit connector
V V V V V
A4 Malfunction of freezing protection Shortage of water volume
Low water temperature setting
Defective water temperature thermistor
V V V V V V
A5 High pressure control in heating, freeze-up protection control in cooling Clogged air filter of indoor unit and short circuit
Defect of indoor unit heat exchanger thermistor
A6
A7
A8
A9
AA
AF
AH
AJ