Daikin

From CoolAutomation Wiki
Jump to navigation Jump to search

Setting Indoor Group Address

Indoor Group Address is required for proper CoolMasterNet operation. Without Group Address Indoor unit is not visible and can not be controlled by CoolMasterNet. Group Address is set with wired remote controller. Here is a simple sequence of operations for Daikin BRCE61 wired remote controller to set Group Address.

  • Press and hold Cancel button for a few seconds

BRC1E61-buttons.gif

  • Scroll down to Group No. setting function and press Menu/Enter button

BRC1E61-group-address-menu.gif

  • Program Group Address and then press Menu/Enter to save address

Remember if Indoor unit can not see a CoolMasterNet you won't have the Group Address menu option. So make sure the CoolMasterNet is wired to F1 F2 HVAC line and powered.

Daikin Self-diagnostic Malfunction (Error) Codes

I
n
d
o
o
r

U
n
i
t
Malfunction

Code

Problem

Description

Supposed

Causes

Models
RA Sky
Air
VRV Pac
kage
HRV Chil
ler
Fan
Coil
A0 External protection device activated External protection device connected to the terminal strip T1-T2 of indoor unit is activated V V V
A1 Malfunction of indoor unit PCB Defective indoor unit PCB
External factor (Noise etc.)
V V V V V V
A2
A3
A4
A5
A6
A7
A8
A9
AA
AF
AH
AJ