CoolMasterNet:UID

From CoolAutomation Wiki
Jump to navigation Jump to search
HVAC
Type
Line(s) Indoor
Number
Examples Notes
X YY
DK L1,L2 1..8 00..15 L1.100 L2.815
SA,TO L1,L2 0..F,Z 01..64 L1.001 L2.F99 To access Indoors via Central Address
ZYY format is used, like L1.Z23
ME L1,L2 0 01..50 L1.001 L2.050
HT L1,L2 1..F 00..63 L1.100 L2.F63
LG L4,L5,L6,L7 0 00..FF L4.000 L7.0FF Indoor Number is Hexadecimal
MH L4,L5,L6,L7 0..1 01..99 L4.000 L7.127 UID range is 000..127
GR L4,L5,L6,L7 1..9 01..16 L4.101 L7.916 Where can be up to 16 Indoors in one system
MD,KT,TR L4,L5,L6,L7
FJ L8 0..F 00..63 L8.000 L8.F63